Short Description:
GN19-12 Indoor High Voltage Isolation Relationship High Voltage Switchgear, used in power systems with rated voltage of 12KV, AC 50Hz and below, equipped with CS6-1 manual operating mechanism, used for opening and closing circuits under voltage and no load conditions. It also has derivative products such as anti fouling type, high prototype type, and installation of live display devices.
summary:
GN19-12 Indoor High Voltage Isolation Relationship High Voltage Switchgear, used in power systems with rated voltage of 12KV, AC 50Hz and below, equipped with CS6-1 manual operating mechanism, used for opening and closing circuits under voltage and no load conditions. It also has derivative products such as anti fouling type, high prototype type, and installation of live display devices.
This series of isolating switches is equipped with CS6-1 manual operating mechanism (isolating switches with panels come with built-in integrated operating mechanism).
This series of isolating switches is of three types, consisting of a chassis, a shaft, a lever, a porcelain pillar insulator, a switch blade, and a terminal block. The rotating shaft is mounted on the chassis and has three pairs of levers welded on it. The levers are connected to a ceramic insulator and a knife chain through a pull rod. The rotating shaft extends out of the chassis, and any section of it can be connected to the operating mechanism.
Type C is a through wall type. Where C1 represents rotation on the through wall side; C2 represents the disconnection on the through wall side; C3 indicates that both sides are on the through wall side.
Normal usage conditions:
◇ Altitude not exceeding 1000m;
Surrounding air temperature: -25 ℃ to+40 ℃;
Relative humidity of the surrounding environment: daily average not exceeding 95%, monthly average not exceeding 90%;
The seismic intensity shall not exceed 8 degrees;
Installation location: No fire, flammable, explosive Places with severe pollution, chemical corrosion, and severe vibration.
Main technical parameters:
Project unit parameters
Rated voltage KV 12
1-minute power frequency withstand voltage to ground KV 42
Fracture 48
Lightning impulse withstand voltage (peak) to ground KV 75
Fracture 85
Rated frequency Hz 50
Rated current A 400 630 1000 1250
Rated short-time withstand current KA 16 20 16 20 25 20 25 31.5
Rated peak withstand current KA 40 50 40 50 63 50 63 80
Rated short-time withstand current duration Main/ground knife S 4/2
Creepage distance MM 300~380
Mechanical lifespan: 2000 times
Appearance and installation dimensions:
Product model A B C D E F
GN19-12/400 450 436 4-14*24 210 230 250 620 660 700 870 900 940
GN19-12/630 490 436
GN19-12/1000/1250 510 530 4-18*28
GN19-12C/400 420 625 4-14*24
GN19-12C/630 460 625
GN19-12C/1000/1250 505 745 4-18*28